319. Support: What amp service is required for Spaguts.com Controllers?

For 110V supply to Spaguts.com Controllers, it requires at least a 20 amp service. To calcualte the max amp draw from the controller, find out the max amp draw from each component that plugs into the controller. This include pump(s), blower, and ozone unit, etc. Each spa component should have a label on it that shows the operating amp(s). The heater draws 11.5A. It only works when the pump is on low speed. Please contact a Licensed Electrician to calculate the total amp draw, and to pull the required amp service to the spa according to electrical code. Failure to provide correct amp service and correct wiring may damage the controller. This will affect the warranty. For 220V supply to Spaguts.com Controllers, it requires a minimum of 50 amp service. For a controller that operates multiple pumps, it may require more than 50 amp service. To calcualte the max amp draw from the controller, find out the max amp draw from each component that plugs into the controller. This include pump(s), blower, and ozone unit, etc. Each spa component should have a label on it that shows the operating amp(s). The heater draws 23A. It will work even when all components are turned on. Please contact a Licensed Electrician to calculate the total amp draw, and to pull the required amp service to the spa according to electrical code. Failure to provide correct amp service and correct wiring may damage the controller. This will affect the warranty.